Reducing Nosocomial Infections in ORs

Article

Reducing Nosocomial Infections in ORs

By Farhad Memarzadeh, PhD, PE and Andy Manning, PhD

The National Institutes of Health (NIH) Office of Research Services, Divisionof Engineering Services, conducted an extensive study on the issue of operatingroom (OR) ventilation systems and their effect on the protection of the surgicalsite.

The risk of nosocomial infection is present in all surgical procedures, butcan be particularly serious in certain operations, such as joint replacement.The many factors that influence infection are shown in Figure 1.

The standards suggested for air conditioning systems for ORs in differentcountries vary widely in content and recommendations and are often based on oldresearch. For example, the ASHRAE Handbook1 is based on workoriginally carried out in the 1950s. As a point of reference, the ASHRAEHandbook suggests that "the delivery of air from the ceiling, with adownward movement to several exhaust inlets located on opposite walls, isprobably the most effective air movement pattern for maintaining theconcentration at an acceptable level."1

The handbook indicates that the temperature range should be between 62degrees Fahrenheit (16.67 Celsius) and 80 degrees F (26.67 C), and that positivepressurization should be maintained. It also suggests that the air should beexhausted or returned from at least two locations near the floor. It suggeststhat supply diffusers should be of the unidirectional type and thathigh-induction ceiling or sidewall diffusers should be avoided. The recommendedACH is 15 ACH for systems that use all outdoor air and 25 ACH for re-circulatingair systems.

Some studies have been published which consider the relative merits ofdifferent systems, such as Lidwell2 and Schmidt.3 However,since they do not include specific system design data, it is difficult toestablish definitive recommendations. Further, while laminar flow systemsprovided lower general concentration levels in the room, they are sometimesblamed for higher infection rates than more conventional systems, for example,Salvati et al.4 The theory put forward by Lewis5 is thatlaminar flow systems cause impingement on the wound site. However, with Schmidtdefining a laminar system as having velocities of at least 90 fpm (0.45m/s),this probably is due to high supply velocities.

The aforementioned studies were experiment based; however, an alternativetechnique, Computational Fluid Dynamics (CFD), sometimes known as airflowmodeling, has been proved to be very powerful and efficient in research projectsinvolving parametric study on room airflow and contaminant dispersion (Ziang, etal.6 and Haghighat et al.7) In the study documented here,airflow modeling is used to consider the dispersion of squame-sized particles(which are recognized as the main transport mechanism of bacteria in operatingrooms (Woods, et al.)8 under various ventilation system-designconditions. To establish the relative ranking of the different systems, twotarget areas of concern are considered: the surgical site and the top surface ofthe back table where instruments are located.

Methodology

TheCFD and particle tracking routine methodology are described in detail inMemarzadeh and Manning.9 (They are not included here because of spacelimitations. A copy of the paper is available at: http://des.od.nih.gov/eWeb/research/farhad/index.htm.)

Outline of Base Model

A typical OR layout was considered for the baseline model. The room measured20 feet (6.1m) by 20 feet (6.1m) by 12 feet (3.66m) high; general features aregiven in Figure 2 and Table 1. The room's layout was agreed upon by a panel ofphysicians and engineers. The total heat dissipated in the room was 2166W.

Model considerations

Several ventilation systems were considered in this study and are shown inTable 2. These systems approximately replicate those outlined in Schmidt.3Models of the various diffuser types considered in this project were allvalidated prior to the room parametric study against manufacturers data.

Contamination consideration

Squames are cells which are released from exposed regions of the surgerystaff and patient, for example, neck, face, etc., and are the primary transportmechanism for bacteria in the OR. They are approximately 25 microns (mm) by 3 to5 microns thick. Approximately 1.15 by 106 to 0.9 to 108 squames are generatedduring a typical (two-hour to four-hour) procedure.10 In this study,the squame particles would be tracked to see how many hit the back table, shownin Figure 3, or the surgical site. The surgical site was taken as a 1-foot(0.3m) by 1-foot (0.3m) square with the surface temperature at 100 degrees F(37.78C), and is shown in Figure 3.

A representative number of particles was introduced from three arrays ofsources in the CFD models. The locations and sizes of the sources, designated asMain, Nurse and Surgery, are shown in Table 3. As the particles could readilypass to the instruments at this point, the surgery source/top surface of backtable target analysis was not performed in this study.

Results

There are three potential particle outcomes:

  • The particle exits the room via exhaust grilles

  • The particle strikes the surgical site or top surface of back table.

  • The particle remains in the room at the time where particle tracking is stopped (one hour)

  • Percentage of particles removed by ventilation varying with time

Table 4 shows there is a wide range of particle removal effectiveness. Casesthat have the same ACH show marked differences in terms of the percentage ofparticles removed via ventilation. For example, Case 10 demonstrates a moreeffective removal of particles than Case 1.The reason is that the ventilationsystem in Case 1 results in the formation of two large re-circulations in theroom where particles can become trapped; this is illustrated in Figure 4. InCase 10 the ventilation system works with the thermal plume in the center of theroom in driving the particles up to the high level exhausts. Taking Cases 3, 4,5, 6 and 9 as a group that adopts the same general approach to ventilation, thepercentage vented from all locations becomes more uniform on increasing ACH andsupply array size. The reason is, for the smaller laminar arrays, the areasoutside the direct influence of the supply have very low velocity flow fields,and particles are more likely to drop to the floor via gravity.

Percentage of Particles, Which Hit Surgical Site or Top Surface of BackTable

Table 5 shows that the percentages of particles which hit the surgical sitefrom the main or nurse sites are low (less than 1 percent) because of therelative dominance of the thermal plume caused by the surgical site. Forexample, Figure 5 shows such a plume for Case 2. It is only when the particlesare released close to the site, in particular, the surgery source, that thepercentage becomes significant. It is also clear that ACH is not as significantin the surgery source/surgical site analysis as design of the ventilationsystem. In particular, a lower percentage of particles hit the site in Case 4,which has an ACH of 20, than Case 2, which has an ACH of 150.

The results also show, with the exception of Case 11, the percentage ofparticles that hit the back table from the main or nurse sites is relativelylow. In Case 11, the particles are blown onto the table. The results for Cases4, 5 and 6 indicate that a mixture of exhaust location levels is better than lowor high only. Finally, the cases which can be placed together in a laminar flowtype group, namely, Cases 2, 3, 4, 5, 6 and 9, show lower strike rates than theother systems. In fact, Cases 4 and 9 represent the lowest strike percentages ofall the cases considered.

Conclusions and Discussion

Conclusions of the study are:

  • Cases which have the same ACH show marked differences in terms of the percentage of particles removed via ventilation.

  • The practice of increasing ACH to high levels results in excellent removal of particles via ventilation, but it does not necessarily mean that the percentage of particles which strike critical surfaces will continue to decrease.

  • The percentages of particles which hit the surgical site from the Main or Nurse sites are low (less than 1 percent). This is because of the relative dominance of the thermal plume associated with the warm surgical site. Only when the particles are released close to the site, in particular, the surgery source, does the percentage become significant.

  • ACH is not as significant as the design of the ventilation system. In particular, a lower percentage of particles hits the site in a case which has an ACH of 20, than one which has an ACH of 150.

  • In a system which provides a laminar flow regime, a mixture of exhaust location levels works better than either low or high level locations only. However, the difference is not significant enough that the low- or high-level location systems are not viable options.

  • Systems that provide laminar flow regimes represent the best option for an operating room in terms of contamination control; however, care needs to be taken in the sizing of the laminar flow array. A face velocity of around 30 to 35 fpm (0.15 to 0.18 m/s) is sufficient from the laminar diffuser array provided that the array size itself is set correctly.

To expand on the issue of diffuser array size, it appears that the mainfactor in the design of the ventilation system is the control of the centralregion of the OR. In particular, the operating lights and surgical staffrepresent a large heat density in the middle of the room. Particulates could getcaught in buoyant plumes created by these heat-dissipating objects, at whichpoint control of them is lost; however, if a laminar flow type system isemployed, the particles are instead driven by the flow to the exhaust. Ideallythen, the array size should be large enough to cover the main heat dissipatingobjects.

This is illustrated in Figure 6, which shows the flow field for Case 9.

Further, another factor is the thermal plume created by the surgical site,shown for Case 2 in Figure 5.A laminar flow regime which provides air at 30-35fpm (0.15 to 0.18 m/s) ensures that particles are not impinged on the surgicalsite, a danger highlighted by Lewis5 as the thermal plume should besufficient to protect the surgical site.

Farhad Memarzadeh, PhD, PE, is chief of technical resources in the Officeof Research Services, Division of Engineering Services at the NationalInstitutes of Health in Bethesda, Md. Andy Manning, PhD, is director ofengineering for Flomerics, Inc. of Southboro, Mass.

Recent Videos
Infection Control Today's Infection Intel: Staying Ahead With Company Updates and Product Innovations.
COVID-19 presentations at IDWeek in Las Angeles, California by Invivyd.   (Adobe Stock 333039083 by Production Perig)
Long COVID and Other Post-Viral Syndromes
Meet Jenny Hayes, MSN, RN, CIC, CAIP, CASSPT.
Infection Control Today Editorial Advisory Board: Fibi Attia, MD, MPH, CIC.
Andrea Thomas, PhD, DVM, MSc, BSc, director of epidemiology at BlueDot
mpox   (Adobe Stock 924156809 by Andreas Prott)
Meet Alexander Sundermann, DrPH, CIC, FAPIC.
Veterinary Infection Prevention
Related Content